Assist Trap/Pumping Trap
PF-7000
1. Non-electric since it utilizes inexpensive steam pressure or air pressure for operation. 2. Maintenance inspection is easily done due to main parts are attached to the cover. 3. Untouchable by hand due to automatic operation after installation. 4. Running costs can be significantly reduced since gas for the operation is consumed only at the time of pumping. |
![]() |
Feature | For middle capacity and large capacity | |
Kind | Pumpimg Trap | |
Specifications | Application | Steam condensate , Non-hazardous fluid |
Driving fluid | Steam / Air | |
Max. driving pressure | 0.8 MPa *1 | |
Max. working temperature | 180 degrees | |
Connection | JIS Rc screwed | |
Check valve at inlet and outlet side | Externally attached *2 | |
Material | Body | Ductile cast iron (FCD450) |
Trim parts | Stainless steel | |
Float (P) | Stainless steel |

*1 The most appropriate value of driving pressure is back pressure at outlet + 0.1 to 0.2 MPa. *2 Attach an optional check valve (SCV-2 or SCV-3) on inlet and outlet side of the product. |
Size | H | L | Weight |
25A(Condensate inlet: 25A / Condensate outlet: 25A) | 620 | 544 | 92 |
40A(Condensate inlet: 40A / Condensate outlet: 40A) | 620 | 549 | 92 |
50A(Condensate inlet: 50A / Condensate outlet: 50A) | 620 | 525 | 91 |
80A(Condensate inlet: 80A / Condensate outlet: 50A) | 620 | 500 | 90 |

![]() |

Drawing (177 KB) |
Instruction manual (1,683 KB) |
CAD external view (192 KB) |